I/P: 3∮,O/P: 3∮Series  |3∮(Phase) on-line|I/P: 3∮,O/P: 3∮Series

I/P: 3∮,O/P: 3∮Series


10KVA ~ 320KVA

Code 10KVA-320KVA

CTR 2126





 

 

FEATURES & ADVANTAGES

True Galvanic isolation designSolve ultimately the problem of power system, including noise, lightning, and leakage current etc.

Protection against detaching and floating of the neutral of input power supplyEnsure the safety and stability of the UPS power output.

No harms if incorrect operationWith friendly design, different from the strict operation procedure of other brands’, UPS will not be damaged by any incorrect operation.

Advanced technology DSP, IGBT and switching componentsIncrease the reliability and efficiency.

Multi-CPU design and software/hardware cooperate controlMake the system extremely high reliable.

Plug & play modular designPermit quick and convenient maintenance.

Each phase with individual inverter supportingCharacteristics will not be violated under 100% unbalance load.

Intelligent charger with temperature compensationProlong the battery life expectancy. And with huge charging power (selectable), can charge very big capacity, long back-up time battery bank.

Intelligent, safe battery test circuitryTest the battery without the risk of output AC failure in case of battery bad. And with battery fluid leakage and improper grounding detect circuitry, can ensure safety of the battery bank.

Intelligent fan speed controlIncrease the fan life expectancy and reduce audible noise.

Reasonable heat evacuation passage designControl circuitry and power circuitry are physically separated. Therefore, the UPS system can operate under harsh environment.

Cool start functionCan be started without AC mains (with battery only) and no any large surge current being drawn.

Variety of accessory (options)Remote control panel, 3 phases software for PC monitoring, auto dialing module, battery monitoring module, 3 phases SNMP card, and emergent stop switch are available.

12-Pulse Full Controlled Rectifier (option)Reduce harmonic current for 80KVA and above UPS.

Input Harmonic Filter (option)Reduce T.H.D.(Total Harmonic Distortion) of input current.

Parallel Operation (option)Connect up to 8 units to increase the capacity.

 

SERIES DIMENSION

 

10KVA-320KVA 10KVA-320KVA 10KVA-320KVA

 

CABINET SPECIFICATION

Battery Cabinet Design:The battery cabinet is designed with the same size and outlook as the UPS for convenience of installation when several cabinets of UPS and battery are aligned together. It can accommodate Lead Acid maintenance free battery 26Ah/12V*29pcs(1set) or 58pcs(2sets).

Dimension (H ×W ×Dmm):1600 ×550 ×800

Weight:26Ah/12V ×29pcs ×1set is about 360kgs.
26Ah/12V ×29pcs ×2sets is about 620kgs.

10KVA-320KVA

 

OPTIONS

l UPSCANTM - Remote Control Penal

A hand held display module with LCD and LED can monitor 1 – 99 UPSs with RS-485 connected in series from distance < 1000M.

l UPSCALLTM - Auto Service Call

In case of abnormal situation, it will automatically dial to specified service center for help. Multiple phone numbers can be set and no dedicated line is required.

l UPSCOMTM - PC Monitoring Software

Can provide real-time three phases information of UPS connected on the line and monitor several UPSs with one PC.

l DCMANTMBattery Monitoring Module

An intelligent module to keep watching each battery in a battery bank connected in series and can distinguish and repair the aged battery before it is seriously worn out.

l SNMP/HTTP agent

Can monitor and manage the UPS through Web browser and Java applet, providing simultaneously three phases data acquisition.

l Emergency Stop Switch

Be installed outside or nearby the UPS for stopping the UPS output in case of emergency.

 

 

PHASE
3-Phase Input / 3-Phase Output
MODEL
3P3-10
3P3-20
3P3-30
3P3-40
3P3-50
3P3-60
3P3-80
3P3-100
3P3-120
3P3-160
3P3-240
3P3-320
KVA
10KVA
20KVA
30KVA
40KVA
50KVA
60KVA
80KVA
100KVA
120KVA
160KVA
240KVA
320KVA
 INPUT (RECTIFIER)
 
Input Voltage
220VΔ / 380VΔ / 460VΔ, 208VY / 380VY / 400VY / 415VY
Input Range
 + / - 20% ( > +/- 20% is available upon request)
Input Frequency
50 / 60 Hz + / - 5Hz
Power Walk In
0% - 100% : 20 sec
Efficiency
98%
Voltage Regulation
 + / - 1%
 BATTERY
 
Battery Type / Pcs
Maintenance free lead-acid batteries / 12V x 29pcs
Maximum Charge
 Current Adc (Selectable)
5
10
15
20
25
30
40
50
60
80
120
160
Battery Start
Yes, UPS can be started without AC source.
 INVERTER
 
Output Voltage
220VΔ / 380VΔ / 460VΔ, 208VY / 380VY / 400VY / 415VY, + / - 1 %
Wave Form
Sine Wave
Output Power Factor
0.8
Frequency Lock Range
50 / 60 Hz + / - 3Hz
Output Frequency
(Free Running)
50 / 60 Hz + / - 0.1 Hz
Phase Shift Under 100%
Unbalance Load
< 0.5°
THD (Linear Load)
< 2 %
Overload
<110%
Continuous
110 – 125%
15 minutes
125 – 150%
10 minutes
> 150%
1 minute
Efficiency (100% Load)
93%
93%
93%
93.5%
93.5%
94%
94.5%
94.5%
95%
95%
95%
95%
 STATIC SWITCH
 
Voltage Range
173-277 VAC (L-N)
Mains ←→ Inverter
0 ms
 OVERALL CHARACTERISTICS
 
Overall Efficiency
91%
91%
91%
91.5%
92%
92%
92.5%
92.5%
93%
93%
93%
93%
Maximum Heat
Dissipation (Kw)
1.1
1.3
1.9
2.6
3
3.5
4.6
5.4
6.5
8.7
13
17.4
Height x Width x Depth (mm)
1600 x 550 x 800
80-160KVA: 1600 x 1100 x 800,
240-320KVA: 1600 x 2200 x 800
Weight (Kg, without battery)
(for standard 380V Y input only)
300
350
400
480
550
680
820
950
1180
1450
1950
2450
Audible Noise
< 65 dBA (At 1 M)
< 67 dBA (At 1 M)
Temperature
0 – 40 ( 32 – 104 )
Humidity
0% - 90% (Non–Condensing)
Altitude
<1500 M Above Sea Level
EN50091-1,-2
YES
Short Circuit Pretection
YES
Lightning / EMC Filter
MOV / Input&Output (FCC CLASS A)
Galvanic Isolation
Input&Output true Galvanic isolation
LED,LCD,Buzzer
YES
Remote Control /
Communication Interface
Monitoring 1~99 UPS simultaneously / Dry contact, RS232, RS485
☆ Different specifications required are available.
☆ All specifications mentioned above are subject to change without prior notice.

Add to inquiry